How Many 4 AWG THHN Wires Fit in 1-1/4" EMT Conduit? (NEC Chart)

Per NEC Chapter 9 Table 4 and Table 5, 1-1/4" EMT has a total internal area of 1.496 sq. in. (40% allowed fill = 0.598 sq. in.), allowing up to 7 4 AWG THHN conductors.

Google AdSense Leaderboard Slot (Activates automatically once you add your Publisher ID in config.js)

Direct NEC Chapter 9 Answer: 7 Conductors Maximum (40% Fill)

7 Wires
Max 4 AWG THHN in 1-1/4" EMT
Standard Run (NEC 40% Fill = 0.598 sq in)
10 Wires
Nipple ≤ 24 Inches (60% Fill)
NEC Chapter 9 Note 4 Nipple Allowance
0.0824 sq in
Single 4 AWG THHN Area
Total 1-1/4" EMT Area: 1.496 sq in

→ Open Interactive NEC Conduit Fill Calculator to mix wire gauges and grounds

1. NEC Conduit Fill Calculator (Chapter 9, Tables 1, 4 & 5)

Recommended Job-Site Materials & Tools for This Run

Trade SizeInternal Dia.Total AreaBundle Fill %Max Primary WiresNEC Status